Digital Controller E5CK CSM E5CK DS E 3 1 Advanced, Compact Digital Controllers IP66/NEMA4 (indoor use) front face. Modular structure, one-stock type. Heating/cooling control. Serial communications (RS-232C and RS-485). Temperature and analog inputs. High-accuracy: 100 ms sampling (for analog input). Advanced tuning which includes fuzzy self-tuning. Conforms to international EMC and safety standards. Refer to E5 K Operation for operating Refer to Safety Precautions for All Temperature Controllers. procedures. Model Number Structure Model Number Legend Refer to the following when ordering set models. E5CK- 1 2 3 4 1. Constant Value/Program 3. Auxiliary Output Blank:Constant value 1: Auxiliary output (1 point) T: Program 4. Option 2. Control Output 1/Control Output 2 01: RS-232C serial communication AA: Without Output Unit (field interchangeable) 03: RS-485 serial communication RR: Relay/Relay B: Event input (1 point) QR: Pulse (NPN)/Relay F: Transfer output (4 to 20 mA) CR: Linear (4 to 20 mA)/Relay VR: Linear (0 to 10 V)/Relay QQ: Pulse (NPN)/Pulse (NPN) Note: E5CK-VR1 and E5CK-QQ1 are not available, but with options. Ordering Information List of Models Description Model Specification Base Unit E5CK-AA1 AC100-240 Base Unit E5CK-AA1-500 AC100-240 Base Unit with terminal cover E5CK-TAA1 AC100-240 Standard model E5CK-TAA1-500 AC100-240 Standard model with terminal cover Note: A single Output Unit and Option Unit can be mounted to each Base Unit. Description Model Specification Output Unit E53-R4R4 Relay/Relay E53-Q4R4 Pulse (NPN)/Relay E53-Q4HR4 Pulse (PNP)/Relay E53-C4R4 Linear (4 to 20 mA)/Relay E53-C4DR4 Linear (0 to 20 mA)/Relay E53-V44R4 Linear (0 to 10 V)/Relay E53-Q4Q4 Pulse (NPN)/Pulse (NPN) E53-Q4HQ4H Pulse (PNP)/Pulse (PNP) 1E5CK Description Model Specification Option Unit E53-CK01 RS-232C E53-CK03 RS-485 E53-CKB Event input: 1 point E53-CKF Transfer output (4 to 20 mA) Inspection Report The Digital Controller can be provided together with an inspection report. Refer to the following legend with the suffix K when ordering a model provided together with an inspection report. E5CK-AA1-K, E53-CKF-K Accessories (Order Separately) Name Model Terminal Cover E53-COV07 Name Model Rubber Packing Y92S-29 Note: The Rubber Packing is provided with the Digital Controller. Specifications Ratings Item 100 to 240 VAC type Supply voltage 100 to 240 VAC, 50/60 Hz Power consumption 15 VA Operating voltage range 85% to 110% of rated supply voltage Input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII Platinum resistance thermometer: JPt100, Pt100 Current input: 4 to 20 mA, 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, 1 to 10 V Input impedance Current input: 150 Voltage input: 1 M min. Control output According to Output Unit (see Output Unit Ratings and Characteristics) Auxiliary output SPST-NO, 1 A at 250 VAC (resistive load) Control method ON/OFF or 2-PID control (with auto-tuning) Setting method Digital setting using front panel keys Indication method 7-segment digital display and LEDs Other functions According to Option Unit (see Output Unit Ratings and Characteristics) Note: 1. Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Temperature Controllers. 2. The E5CK-T does not support fuzzy self-tuning. Input Ranges Platinum Resistance Thermometer Input (switch selectable) JPt100 Pt100 Range C 199.9 to 650.0 199.9 to 650.0 F 199.9 to 999.9 199.9 to 999.9 Resolution (C/F) 01 (main setting and alarm) 2