Motor Timer H2C CSM H2C DS E 2 1 DIN-sized 48 x 48 Motor Timer with Simple Operation for Switching Time Specifications Three Motor Timers cover the wide time range of 6 s to 30 h with easy operation from the operation panel. Five time specifications for each model with linked time display. DIN-standard size of 48 x 48 mm. Easily check operation with neon lamp. Models with sockets and models with top wiring are also avail- able. Certified for UL and CSA safety standards. Conforms to EN 61812-1 (except models that end with -F) and CE Marking. Model Number Structure Model Number Legend H2C- 12 1. External Connection/Attachment 2. Operation/Resetting System None: 11-pin socket None: Time-limit operation/self-resetting S: 11-pin socket/time setting ring R: Time-limit operation/electric resetting 8: 8-pin socket F: Front screw Ordering Information List of Models Operation/resetting Internal Terminal Time-limit Instantaneous Attachment Model system connection contact contact Time-limit operation/ Parallel motor and 8-pin socket SPDT SPDT --- H2C-8 self-resetting clutch connection Separate motor 11-pin socket H2C and clutch Y92A-Y1 Time H2C-S connection Setting Ring Front screw --- H2C-F Time-limit operation/ 8-pin socket SPDT --- --- H2C-8R electric resetting 11-pin socket SPDT H2C-R Y92A-Y1 Time H2C-SR Setting Ring Front screw --- H2C-FR Note: Specify both the supply voltage and time range code (A, B, or C) in addition to the model number when ordering. Example: H2C-S 24 VAC B Time range code Supply voltage 1H2C Accessories (Order Separately) Name/specifications Models Flush Mounting Adapter Y92F-30 Time Setting Ring (See note 1.) Y92A-Y1 Mounting Track 50 cm (l) 7.3 mm (t) PFP-50N 1 m (l) 7.3 mm (t) PFP-100N 1 m (l) 16 mm (t) PFP-100N2 End Plate PFP-M Spacer PFP-S Protective Cover Y92A-48B Track Mounting/Front Connecting 8-pin P2CF-08 Socket 8-pin, finger safe type P2CF-08-E 11-pin P2CF-11 11-pin, finger safe type P2CF-11-E Back Connecting Socket 8-pin, screw terminal P3G-08 8-pin, finger safe type P3G-08 with Y92A-48G (See note 2.) 11-pin P3GA-11 11-pin, finger safe type P3GA-11 with Y92A-48G (See note 2.) Hold-down Clip (See note 3.) For PL08 and PL11 Sockets Y92H-1 For PF085A Socket Y92H-2 Note: 1. Supplied with H2C-S/-SR models. 2. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket. 3. Hold-down Clips are sold in sets of two. Specifications Time Ranges Five time ranges are available for each timer by turning the time range selector every 60 degrees. Note: Rated time is displayed on the window. Time range code Position of time range selector A 1.25 to 30 s 7.5 s to 3 min 1.25 to 30 min 7.5 min to 3 h 1.25 to 30 h B 0.2 to 6 s 2 to 60 s 0.2 to 6 min 2 to 60 min 0.2 to 6 h C 0.5 to 12 s 5 to 120 s 0.5 to 12 min 5 to 120 min 0.5 to 12 h Ratings Item H2C Rated supply voltage (motor and 24, 48, 100, 110, 115, 120, 200, 220, or 240 VAC (50/60 Hz) (see note) clutch) Operating voltage range 85% to 110% of rated supply voltage Power consumption 4.2 VA max. (3.96 W max.) Reset voltage 10% max. of rated supply voltage Reset time Minimum power-opening time:0.5 s Minimum pulse width: 0.5 s Control outputs 6 A at 250 VAC, resistive load (cos = 1) Mounting method Flush mounting (except for H2C-F/-FR models), surface mounting, DIN track mounting Note: The front panel of the timer is color coded to identify the following supply voltage classifications: 100 to 120 V: Blue 200 to 240 V: Red Other classes: Black 2