DRF120-960 Series 120-960W, 24V Output DIN Rail Mount Power Supplies Features Very Compact Size High E ciency (Up to 95%) 150% Peak Power Capability for 4s ErP Compliant Design Low Standby Power Draw Remote On/O Remote Voltage Adjustment Hazardous Location Option (/HL) Key Market Segments & Applications Speci cations Model DRF120 DRF240 DRF480 DRF960 (1) Input Voltage Range V 85 - 264VAC, 125 - 370VDC* 180 - 264VAC Input Frequency Hz 47 - 63Hz Inrush Current (typ) (Cold Start) A 20 Power Factor (115/230VAC) - 0.98 / 0.95 0.98 / 0.95 0.98 / 0.92 - / 0.98 (Meets EN61000-3-2) Input Current (115/230VAC) A 1.2 / 0.6 2.4 / 1.2 4.7 / 2.5 - / 4.5 Line Regulation mV <96mV Load Regulation mV <240mV (2) Ripple & Noise mV <240mV Overcurrent Protection - >101% of peak current rating. Shutdown after 4 seconds Overvoltage Protection - 30 - 35.5V, (31.5 - 34V for DRF960). Cycle input voltage or remote on/o to reset Hold Up Time (230VAC input) ms > 20ms >10ms E ciency (115 / 230VAC) % 89 / 91 92.5 / 94 92.5 / 94 - / 95 Standby Power Draw W <0.5W <0.5W <0.75W <1W LED Indicators - Green LED = DC is OK (>80% Nom). Red LED = Peak Load Operation DC OK relay - Relay contact 30V/1A Remote On / O - When signal is low, the output is On Remote Voltage Adjust - 5 - 6V voltage programs output from 24 - 28V o o o Operating Temperature C -25 to +70 C. Start up at -40C. Derate linearly to 75% load above 60 C (50 C for DRF960) Storage Temperature C -40 to +85C Operating Humidity (non condensing) %RH 5 - 95%RH Parallel Operation - Droop Mode - Refer to Installation Manual Series Operation - Possible Cooling - Convection Withstand Voltage (For 1 minute) VAC Input to Output 3kVAC, Input to GND 1.5kVAC, Output to GND 500VDC (960W : 500VAC) Isolation Resistance M >100M at 25C, 70%RH & 500VDC 2 Vibration (Non operating) - 10-55Hz (sweep for 1 min) 19.6m/s (2G) Constant X,Y,Z each 1 hour 2 Shock - <196m/s (3) Safety Agency Certi cations - UL508 Listed, IEC/UL/CSA/EN62368-1 (DRF120-480 only), IEC/UL/CSA/EN61010 (DRF960 only - contact sales), IEC/UL/CSA/EN60950-1, CE Mark, ATEX, IEC Ex. Class 1 Div 2, Group A, B, C, D (DRF120-480) Conducted & Radiated EMI - EN55032-B Radiated & Conducted Immunity - EN61000-4-2 (contact lvl 2, air lvl 3) , -3 (lvl 3), -4 (lvl 3) -5 (norm mode lvl 3, com mode lvl 4), -6 (lvl 3), -8 (lvl 4), -11 Line Dips - SEMI-F47 (200VAC input, 120-480W only) Weight (Typ) g 600 900 1300 1735 Size (WxHxD) in 1.44 x 4.86 x 4.53 1.93 x 4.86 x 4.53 3.23 x 4.86 x 4.53 4.33 x 4.86 x 5.47 Mounts on TS-35/7.5 or -35/15 rail mm 36.5 x 123.4 x 115 49 x 123.4 x 115 82 x 123.4 x 115 110 x 123.4 x 139 Case material - Metal Warranty yrs Five years (1) Withstands 300VAC for 5s (2) See installation manual (3) See options table *Safety certi ed for AC input only (4) Operating period at peak output current is 4 sec, max duty cycle <35% & < rated output powerDRF120-960 Series Model Selector Output Adjust Max Max Peak Output Peak Output (4) (4) Model Voltage Range Current Power Current Power DRF120-24-1 24V 24 - 28V 5A 120W 7.5A 180W DRF240-24-1 24V 24 - 28V 10A 240W 15A 360W DRF480-24-1 24V 24 - 28V 20A 480W 30A 720W DRF960-24-1 24V 24 - 28V 40A 960W 60A 1440W Outline DRF120-24-1 Outline DRF240-24-1 (7.0) (7) 115.41 115.41 (32.3) (34) (16.3) SIGNAL CONNECTOR SIGNAL CONNECTOR (16.3) 491 36.51 (12.1) 6.4 DINRAIL BRACKET (6.4) (11.6) DINRAIL BRACKET 7 - M3 7 - M3 OUTPUT VOLTAGE OUTPUT VOLTAGE ADJUSTMENT ADJUSTMENT DC OK INDICATOR DC OK INDICATOR (GREEN LED) (GREEN LED) PEAK INDICATOR DRF240-24-1 PEAK INDICATOR DRF120-24-1 (11.8) (11.8) Input Details Input Details (RED LED) -25C to 70C (RED LED) 100-240VAC 2.7A -25C to 70C 100-240VAC 1.5A Wiring must be Wiring must be Frequency: 50 / 60Hz >75C rated BAR CODE (12.2) Frequency: 50 / 60Hz >75C rated BAR CODE (12.2) Output Details Le cblage doit tre Output Details Le cblage doit tre >75C nominale EHFP >75C nominale EHFP DC 24-28V/10-8.6A DC 24-28V/5-4.3A FRONT SEAL Maximum power: 240W FRONT SEAL Maximum power: 120W Cau on: For use in a controlled environment, Cau on: For use in a controlled environment, refer to manual for condi ons. refer to manual for condi ons. A en on: Pour une u lisa on dans un environnement contrl,reportez-vous A en on: Pour une u lisa on dans un au manuel d instruc ons pour les condi ons. environnement contrl,reportez-vous IND.CONT.EQ. au manuel d instruc ons pour les condi ons. R E362999 IND.CONT.EQ. R E362999 RISK OF ELECTRIC SHOCK RISK OF ELECTRIC SHOCK Read manual PA619-04-02 Further informa on at: Made in Malaysia Read manual PA618-04-02 emea.tdk-lambda.com/PA619-04-01 Further informa on at: emea.tdk-lambda.com/PA618-04-01 Made in Malaysia NAME PLATE NAME PLATE (15.8) (9.5) (10.5) (16.1) (9.5) (8.8) Outline DRF480-24-1 Outline DRF960-24-1 (7.0) 115.41.0 SIGNAL CONNECTOR (13.0) 82.01 (16.3) (6.4) (27.4) DINRAIL BRACKET 9 - M3 OUTPUT VOLTAGE ADJUSTMENT DC OK INDICATOR (GREEN LED) (7.8) (6.0) (11.8) PEAK INDICATOR DRF480-24-1 Input Details (RED LED) 100-240VAC 5.4A -25C to 70C (12.2) Frequency: 50 / 60Hz Wiring must be BAR CODE >75C rated Output Details Le cblage doit tre >75C nominale EHFP FRONT SEAL DC 24-28V/ 20-15.4A Maximum power: 480W Cau on: For use in a controlled environment, refer to manual for condi ons. A en on: Pour une u lisa on dans un environnement contrl,reportez-vous au manuel d instruc ons pour les condi ons. IND.CONT.EQ. R E362999 RISK OF ELECTRIC SHOCK DRF480-24-1 Read manual PA620-04-02 Further informa on at: emea.tdk-lambda.com/PA620-04-01 Made in Malaysia NAME PLATE (9.5) (10.5) (16.1) Options For additional information, please visit