Date:- 18 Mar, 2005 Data Sheet Issue:- 1 Ultra Rapid Semiconductor Protection Fuse European Square Body Type Fuses French Standard End Contacts Voltage Ratings 450V - 690V Current Ratings 40A 2500A aR Characteristics Sizes 0, 1, 2, 3 Key Features: Extremely high interrupting rating fuses for the protection of power semiconductors in accordance with IEC Standard 60269.1 and 4. 2 Exceptionally low I t, power losses Highly reliable low voltage trip indicator system Non Magnetic construction Conform to UL, IEC, DIN and VDE standards Increased technical performance gives higher ratings and reduction in volume and weight All models available with integrated trip-indicator Microswitch system reference MS 3V 1-5 Data Sheet 069URxSxxxxB Issue 1 Page 1 of 8 March, 2005WESTCODE An IXYS Company French Standard End Contact Fuses Main Characteristics: Total Voltage Current Pre-arcing Clearing Watt Losses Tested Interrupting 2 Size Rating Ref: rating I t 1 ms 2 I t U 0.8I I rating 2 2 N N N U (V) I (A) I t (10 kA s) N N p 2 (10 kA s) 40 069UR0S0040B 0.11 0.68 3 5.5 50 069UR0S0050B 0.12 0.68 4.5 9 63 069UR0S0063B 0.20 1.1 7.5 14 80 069UR0S0080B 0.33 1.75 9.5 19 100 069UR0S0100B 0.47 2.5 13 26 125 069UR0S0125B 0.85 4.5 15 30 160 069UR0S0160B 1.6 8.5 18.5 37 200kA 690V 0 690V 200 069UR0S0200B 3 15.5 21.5 43 250 069UR0S0250B 5.8 30 25 50 315 069UR0S0315B 12 62 22.5 55 350 069UR0S0350B 15.5 80 30 60 400 069UR0S0400B 23 120 32.5 65 450 069UR0S0450B 26 150 44 88 500 069UR0S0500B 41 240 44 88 550 069UR0S0550B 52 300 45 90 Notes: Minimum operating voltage for integrated trip indicator = 20V Microswitch Reference : MS 3V 1-5 Total Voltage Current Pre-arcing Clearing Watt Losses Tested Interrupting 2 Size Rating Ref: rating I t 1 ms 2 I t U 0.8I I rating 2 2 N N N U (V) I (A) I t (10 kA s) N N p 2 (10 kA s) 160 069UR1S0160B 1.3 7.7 27.5 35 200 069UR1S0200B 2.6 13.5 22.5 45 250 069UR1S0250B 4.7 25 25.5 52 315 069UR1S0315B 7.5 40 32.5 65 350 069UR1S0350B 10.5 55 33.5 67 400 069UR1S0400B 19 100 34 68 1 690V 200kA 690V 450 069UR1S0450B 26.5 140 35 70 500 069UR1S0500B 37 195 36 72 550 069UR1S0550B 52 280 37.5 75 630 069UR1S0630B 75 390 42.5 85 700 069UR1S0700B 95 490 85 95 800 069UR1S0800B 140 800 52.5 105 Notes: Minimum operating voltage for integrated trip indicator = 20V Microswitch Reference : MS 3V 1-5 Data Sheet: 069URxSxxxxB - Issue 1 Page 2 of 8 March, 2005