DIN Rail Mount
Datasheet
DRC Series
7.6 Amp AC Semiconductor Motor Controller
Load voltage range up to 600 VAC
Fits standard 35mm DIN Rail
LED input status indicator
AC or DC control
Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
C-UL-US Listed, IEC Rated, CE & RoHS Compliant, Horsepower Rated
Built-in Overvoltage Protection
Ultra-efficient thermal management design (Patented)
Start / Stop Reversing
Solicon DRC3 Series are Solid State Contactors intended for instantaneous change of direction is commanded, then it will
frequently switching on and off three phase loads up to 5 HP, 600 delay the direction change by 100msec in order to prevent
VAC 7.6 Amps. They are available in both contactor versions simultaneous forward and reverse operations.
DRC3P and reversing contactor versions DRC3R.
All the models of Solicon DRC3 Series combine the benefits and
The Solicon Contactor DRC3P is available in either instantaneous advantages of a solid state contactor with the functionality and
turn-on (for Motor Control) or zero voltage turn-on (for Resistive simplicity of use of an electromechanical contactor thanks to the
Loads). It is available in either 2 or 3 controlled leg versions. The proprietary thermal management technology (Patented) and
2 legs control version is particularly suitable for motor control complete electrical insulation (no grounding required); the
circuits where the neutral conductor is not utilized. embedded auxiliary contacts, normally open and/or normally
closed, are intended to be used at 18-280VAC. Five different
The Solicon Reversing Contactor DRC3R includes an interlock
control voltages are available in order to cover most applications.
control that allows only off, forward and reverse operation in a
All models include overvoltage protection.
safe mode while providing high space saving; it switches
instantaneously upon application of the control voltage unless an
PRODUCT SELECTION
Control Voltage Without Auxiliary Contact 1 NO+NC Auxiliary Conctat 2 NO Auxiliary Contact
230 VAC DRC3P48A400, DRC3R48A400 DRC3P48A411 DRC3P48A420, DRC3R48A420
120 VAC DRC3P48B400, DRC3R48B400 DRC3P48B411 DRC3P48B420, DRC3R48B420
48 VAC/DC DRC3P48C400, DRC3R48C400 DRC3P48C411 DRC3P48C420, DRC3R48C420
24 VAC/DC, 24 VAC DRC3P48D400, DRC3R48D400 DRC3P48D411 DRC3P48D420, DRC3R48D420
24 VDC DRC3R48E400 DRC3R48E420
AVAILABLE OPTIONS
Operating Voltage Load Current per Phase
40: 400 VAC 4: 7.6 Amp FLA
(3R function only) (x2 Controlled Legs
Switching Mode
48: 480 VAC & 3R function);
(3P function only)
60: 600 VAC
4.8 Amp FLA Blank: Zero Voltage Turn-On
(3P function only)
Series
(x3 Controlled Legs only) R: Instantaneous Turn-On
DRC 3P 48 D 4
00 R 2
Function Control Voltage Auxiliary Contacts, Controlled Legs
3P: Contactor A: 208-265 VAC N.O. - N.C. (3P function only)
3R: Reversing Contactor B: 90-140 VAC 00: Not included Blank: 3 Controlled Legs
C: 36-55 VAC/DC 11: 1 Solid State Auxiliary 2: 2 Controlled Legs
D: 18-30 VAC/DC Contact, Normally Open;
(3P function only) 1 Solid State Auxiliary
18-30 VAC Contact, Normally Closed
(3R function only) (3P function only)
Required for valid part number E: 18-30 VDC 20: 2 Solid State Auxiliary
(3R function only) Contacts, Normally Open
For options only and not required for valid part number
FDE-07-01 REV. A
Do not forget to visit us at: www.crydom.com
Copyright 2018 Crydom Inc. Specifications subject to change without notice.DIN Rail Mount
Datasheet
(1)
OUTPUT SPECIFICATIONS
Description DRC3P48x4x DRC3P48x4x2 DRC3P60x4x DRC3P60x4x2 DRC3R40x4x DRC3R48x4x
Operating Voltage (47-63Hz) [Vrms] 48-530 48-530 48-600 48-600 48-415 48-510
Transient Overvoltage [Vpk] (2)(3) 1200 1200 1200 1600
1200 1200
Maximum Off-State Leakage Current @ Rated Voltage [mArms] 3.0 3.0 1.0 1.0 5.5 5.5
Maximum Off-State dv/dt @ Maximum Rated Voltage [V/sec] 500 500 500 500 500 500
Load Current, General Use UL508 /AC51 @40C [Arms] (4) 5 7.6 5 7.6 7.6 7.6
Load Current, Motor Controller UL508 /AC-53a @480VAC [Arms] (4) 4.8 7.6 4.8 7.6 7.6 7.6
Minimum Load Current [Arms] 0.15 0.15 0.15 0.15 0.15 0.15
Maximum Surge Current [Apk] 1 Cycle 60Hz 750 750 750 750 750 625
Maximum Surge Current [Apk] 1 Cycle 50Hz 716 716 716 716 716 597
2 2
Maximum I t for Fusing (8.33msec)[A sec] 2330 2330 2330 2330 2330 1621
2 2
Maximum I t for Fusing (10msec)[A sec] 2560 2560 2560 2560 2560 1779
Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.35 per channel 1.35 per channel 1.35 per channel 1.35 per channel 1.5 per channel 1.5 per channel
Minimum Power Factor (with Maximum Load) 0.5 0.5 0.7 0.7 0.5 0.5
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 240 VAC 1/.75 2/1.5 1/.75 2/1.5 2/1.5 2/1.5
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 400 VAC 2/1.5 3/2.2 2/1.5 3/2.2 3/2.2 3/2.2
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 480 VAC 3/2.2 5/3.7 3/2.2 5/3.7 - 5/3.7
Motor Ratings @ 600 VAC [HP/kW] - - 3/2.2 5/3.7 - -
(1)
INPUT SPECIFICATIONS
Description Option A Option B Option C Option D Option E
Control Voltage Range (5) 208-265 VAC 90-140 VAC 36-55 VAC / VDC 18-30 VAC / VDC 18-30 VDC
Minimum Turn-On Voltage (6) 208 VAC 90 VAC 36 VAC / VDC 18 VAC / VDC 18 VDC
Must Turn-Off Voltage 40 VAC 10 VAC 4 VAC / VDC 4 VAC / VDC 4 VDC
Minimum Input Current (for on-state) [mA] 6.1 7.5 12 12.5 12.5
Maximum Input Current [mA] 8 13 20 32 32
Nominal Input Impedance [Ohms] 33k 12.5k 3k 0.93k 0.93k
Maximum Delay to Turn-On [msec] (7) 30 30 30 20 100 30
Maximum Turn-Off Time [msec] (8) 40 40 40 30 20
(1)
SOLID STATE AUXILIARY CONTACTS
Description Normally Open Sufx 2x,1x Normally Closed Sufx x1
Operating Voltage Range (47-63Hz) [Vrms] (9) 18-280 18-280
Transient Overvoltage [Vpk] 600 600
Maximum Load Current [Arms] 1 1
Minimum Load Current [mA] 5 5
Maximum Surge Current [Apk] 1 Cycle 60Hz 40 40
Maximum Surge Current [Apk] 1 Cycle 50Hz 38 38
2 2
Maximum I t for Fusing (8.33msec)[A sec] 6.7 6.7
2 2
Maximum I t for Fusing (10msec)[A sec] 7.2 7.2
Maximum Off-State Leakage Current @ Rated Voltage [mArms] 0.1 5 mA
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/sec] 500 500
Maximum Delay to Turn-On [msec] (7) 30 80
Maximum Turn-Off Time [msec] 40 40
(1)
GENERAL SPECIFICATIONS
Description Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) (10) 3750 Vrms
9
Minimum Insulation Resistance (@ 500 VDC) 10 Ohms
Maximum Capacitance, Input/Output 20 pF
Ambient Operating Temperature Range (11) -30 to 80 C
Ambient Storage Temperature Range -40 to 100 C
Weight (typical) 2 Controlled Legs (6.9 oz [197 g]) / 3 Controlled Legs (8.0 oz [228 g])
Housing Material UL94 V-0
Housing Color Black and Light Gray
LED Status Indicator (color) (12) Forward (Green) / Reverse (Amber)
Short Circuit Current Rating (13) 100kA
MTBF (Mean Time Between Failures) at 40C ambient temperature (14) 1,398,000 hours (159 years)
MTBF (Mean Time Between Failures) at 60C ambient temperature (14)
390,000 hours (44 years)
Pollution Degree 2
Protection Degree (15)
IP20
Humidity 85% non-condensing
Control and Auxiliary Contact Terminal Screw Torque Range (in-lb/Nm) 12 / 1.36
Load Terminal Screw Torque Range (in-lb/Nm) 15 / 1.7
2
Input Terminal Wire Capacity 18-12 AWG (IEC 1-4 mm ) (stranded /solid)
2
Output Terminal Wire Capacity 18-10 AWG (IEC 1-6 mm ) (stranded /solid)
Do not forget to visit us at: www.crydom.com
Copyright 2018 Crydom Inc. Specifications subject to change without notice.