C-SC-Series eries
REMOTE OPERATED CIRCUIT BREAKER
The C-Series remote operated circuit breaker consists of a custom designed remote operated motor module
(housed within a circuit breaker molding) coupled to a C-Series hydraulic-magnetic circuit breaker. The remote
operated circuit breaker (ROCB) offers the convenience of remote ON, OFF, and Reset capability combined
with the safety and accuracy of a standard magnetic current sensing device. This allows operation of the circuit
breaker from various locations in a system, facility or site without sacrificing the ability to manually operate the
breaker if required. Service, diagnostics, load shedding and power distribution control functions can now be
performed in areas that were previously unattended, inaccessible.
The ROCB module can be mounted on either side of the host breaker, while occupying only the width of a
standard C-Series pole. Several interface methods are available.
Product Highlights: ROCB Motor Specifications:
ON-OFF and trip indication Voltage input: 12 VDC to 80 VDC
Load shedding Start current: < 1 amp
Energy management Switching time: < 2 seconds
Compact size Operating Temperature: -25C to 80C
Automatic reset capable
Choice of interface styles
Panel mounting
Manual Operation Override
Fits into industry standard cut-out
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com www.carlingtech.com
Application Support: team2@carlingtech.com
Phone: 860.793.9281 Fax: 860.793.9231| Circuit Breaker Accessories - ROCB - Ordering Scheme
2
To order a remote operated circuit breaker, add / plus the remote module part number to the end of the
C-Series circuit breaker catalog number. ex. CA1BO24620121C/RB1110BU1C
Match color & mounting inserts of breaker.
/
RB 1 1 10 B U 1 C
1 2 3 4 5 6 7 8
Series Mounting Interface Lead Length Voltage Actuator Mounting Agency
Position Rating Color Insert Approval
1 SERIES 5 VOLTAGE RATING
RB A 12 VDC
B 20-40 VDC
C 41-80 VDC
2 MOUNTING POSITION
As viewed from back of breaker, line side up, pole 1 left.
6 ACTUATOR COLOR
1 Left Side
T White
2 Right Side
U Black
V Red
3 INTERFACE W Yellow
1 Flying Leads
2 Integral Connector
7 MOUNTING INSERT
3 Flying Leads with 4 pin dual row connector (female)
1 6-32 x 0.195
4 Flying Leads with 4 pin dual row connector (male)
2 ISO M3 x 5mm
4 LEAD LENGTH 10 10 21 21
8 AGENCY APPROVAL
00 No Lead 11 11 22 22
C UL Recognized & CSA Accepted
01 1 12 12 23 23
E TUV Certified, UL Recognized & CSA Accepted
02 2 13 13 24 24
G UL 489 Listed & CSA Certified
03 3 14 14 25 25
I UL 1500 Ignition Protected,UL Recognized & CSA Accepted
04 4 15 15 26 26
J UL 489 Listed, CSA Certified & TUV Certified
05 5 16 16 27 27
06 6 17 17 28 28
Notes:
07 7 18 18 29 29
Integral and 4-pin dual row connectors not available with agency approval J or G: UL 489.
08 8 19 19 30 30
09 9 20 20
*Manufacturer reserves the right to change product specification without prior notice.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com