Protection Relays and Controls Arc-Flash Monitoring AF0100 SERIES Arc-Flash Relay Description The AF0100 Series arc-flash relay is a cost-effective solution that reduces arc-fault damage by detecting the light from an arc flash and rapidly tripping. Two remote light sensors can be connected to one relay and multiple AF0100 and/or AF0500 relays can be connected to monitor additional sensors, providing complete coverage for a wide range of applications. The compact, DIN-rail or surface-mountable body makes this an ideal solution for equipment manufacturers. Two isolated Form-C contacts are provided for applications with multiple devices that must be tripped. This is especially useful for generator applications where the generator and breaker need to be tripped in case of an arc flash. The AF0100 accepts PGA-LS10 point sensors and PGA-LS20/ PGA-LS30 fiber-optic sensors in any combination. Sensor health is continuously monitored to ensure fail-safe operation. A solid-state redundant trip circuit provides an internal fail-safe Simplified Circuit Diagram mechanism and fast arc-flash response during power up. Front-panel and sensor LEDs indicate sensor health and Digital I/O Connection to other AF0100 or AF0500 fault location. 24-48 Vdc Features & Benefits A PGA-LS10 Supply (Point Sensor) FEATURES BENEFITS + Compact Fits into a wide range of arc-flash applications AF0100 B or PGA-LS20/ (Arc-Flash Protection Relay) Two optical Point sensors or fiber-optic sensors can be used in PGA-LS30 sensor types any combination for coverage flexibility L1 (Fiber-Optic Sensor) Unit Healthy Trip 1 Trip 2 Dual sensor inputs One relay can monitor two arc-flash sensors L2 100-240 Vac/Vdc Adjustable light Allows for operation in bright environments and Supply sensitivity maximum sensitivity in dark environments Discrete wire Multiple AF0100 or AF0500 units can be networking interconnected to form a system Continuous monitoring of optical sensors and Fail-safe system inputs ensures protection Ordering Information Configuration software is easy to use with no ORDERING NUMBER DESCRIPTION USB interface drivers or software installation AF0100-00 Arc-Flash Relay, Universal Supply Ensures continuous protection with self diagnostic Unit health and remote unit-healthy indication AF0100-10 Arc-Flash Relay, 24-48 VDC Trip and sensor status indication both on relay LED Indication and sensors Specifications Accessories Input Voltage PGA-LS10 Point Sensor A AF0100-00 100-240 VAC/VDC, 24-48 VDC Line-of-sight light sensor detects an arc as small AF0100-10 24-48 VDC as 3 kA within a 2-m half-sphere. Includes sensor Dimensions H 90 mm (3.5) W 128 mm (5.0) health and trip indication. D 60 mm (2.4) B Trip, Error Relays Form C, 250 VAC/30 VDC, 6 A resistive PGA-LS20/PGA-LS30 Fiber-Optic Sensor Trip Time 5 ms (typical) 360 light sensor to run along bus bars. Includes sensor health and trip indication. Sensitivity 10-25 klux programmable Mounting Surface, DIN rail Operating Temperature -40C to +70C (-40F to 158F) Shipping Weight 1.0 kg (2.2 lb) Certifications UL Listed (UL 508), CE, RCM, FCC Warranty 2 years 2017 Littelfuse Protection Relays & Controls Rev: 1-B-012517 www.littelfuse.com/af0100 Based on Manual Rev 0X-ON Electronics Largest Supplier of Electrical and Electronic Components Click to view similar products for littelfuse manufacturer: Other Similar products are found below : V130LA10A 1SMB33AT3G 1SMA24AT3G 59022-3-S-02-F 59022-3-U-02-E FLEX-14-35-40 SK225RDTP GTCA28-231M-R05 00970019XP LX5090 0224006.HXUP 740GN 815.650 FLA2.25 FLSR400 FLSR600 900-1535-012RN 901-134 970699013 971-670A- 92WCN 153.5631.5601 155100 1.5KE110A-B 1.5KE220A 1.5SMC150CA BLF006 BLF008 JLLS-250 235.200 901-152C-042RN 920- 401X-330BN 282007 LFC600602CID LFR600303CID LJCA030.X SE-GRM024 980-788A-070 FLNR100 FLNR400 FLSR200 211RT 224007 225.250 CCMR-2 239002 CG110L Q6012LH1LED 30KPA150CA-B R460.375 313.25