Product data sheet GV2ME163 Characteristics TeSys GV2 Manual Starter and Protector, thermal magnetic circuit protector, push buttons, 9...14 A, spring terminals Product availability: Stock - Normally stocked in distribution facility Main Range TeSys Product name TeSys GV2 Device short name GV2ME Device application Motor Trip unit technology Thermal-magnetic Complementary Poles description 3P Network type AC Utilisation category AC-3 conforming to IEC 60947-4-1 Category A conforming to IEC 60947-2 Network frequency 50/60 Hz conforming to IEC 60947-4-1 Fixing mode Clipped on 35 mm symmetrical DIN rail Screwed on panel (with adaptor plate) Operating position Any position Motor power kW 7.5 kW at 500 V AC 50/60 Hz 5.5 kW at 400/415 V AC 50/60 Hz Breaking capacity 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 Ics rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 Control type Push-button In rated current 14 A Thermal protection adjustment range 9...14 A Magnetic tripping current 170 A System Voltage AC 50/60 Hz conforming to IEC 60947-2 Ui rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 Ith conventional free air thermal current 14 A conforming to IEC 60947-4-1 Uimp rated impulse withstand voltage 6 kV conforming to IEC 60947-2 Power dissipation per pole 2.5 W Mechanical durability 100000 cycles Electrical durability 100000 cycles AC-3 at 440 V Operating rate 25 cyc/h Rated duty Continuous conforming to IEC 60947-4-1 Connections - terminals Spring terminals 2 cable(s) 0...0.01 in (1...6 mm) solid Spring terminals 2 cable(s) 1.5...4 mm flexible without cable end Suitability for isolation Yes conforming to IEC 60947-1 Aug 15, 2019 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Phase failure sensitivity Yes conforming to IEC 60947-4-1 Height 3.98 in (101 mm) Width 1.77 in (45 mm) Depth 3.08 in (78.2 mm) Product weight 0.62 lb(US) (0.28 kg) Environment Standards NF C 79-130 VDE 0660 IEC 60947-4-1 CSA C22.2 EN 60204 IEC 60947-1 UL 508 VDE 0113 IEC 60947-2 NF C 63-650 NF C 63-120 Product certifications UL BV SETI ATEX DNV GL LROS (Lloyds register of shipping) CCC EZU EAC CSA RINA TSE CEBEC Protective treatment TH IP degree of protection IP20 conforming to IEC 60529 IK degree of protection IK04 Ambient air temperature for operation -4...140 F (-20...60 C) Ambient air temperature for storage -40...176 F (-40...80 C) Fire resistance 1760 F (960 C) conforming to IEC 60695-2-1 Operating altitude 6561.68 ft (2000 m) Ordering and shipping details Category 22367 - MANUAL STR PROTECTOR - GV2 Discount Schedule I11 GTIN 00785901212195 Nbr. of units in pkg. 1 Package weight(Lbs) 0.70999999999999996 Returnability Y Country of origin FR Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 0631 - Schneider Electric declaration of conformity Schnei- der Electric declaration of conformity REACh Reference contains SVHC above the threshold - Go to CaP for more details- Go to CaP for more details Product environmental profile Available Product end of life instructions Need no specific recycling operations California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. - - - - - - - More information For more information go to www.p65warnings.ca.gov 2