Industrial Control Transformers
International Series Control Transformers: 50 - 750 VA
Electromagnetic control components demand inrush  
currents up to 10 times the transformers nominal rating  
without sacrificing secondary voltage stability beyond  
practical limits. The International series transformers fully 
comply with IEC and NEMA standards and are available  
with IEC touchproof covers (IP20). 
Features
 Epoxy encapsulated for cooler operation
 Interleaved copper windings to reduce impedence 
 50/60 Hz
 55C Rise, 105C insulation system for harsh,  
heavy duty applications
 Exceeds IEC, NEMA, ANSI, NMTBA, JIC and  
automotive standards
Certifications and Compliances
E77014
 Listed: E77014 - Type SBE
- UL 5085-1, UL 5085-2
- CSA C22.2 No. 66.1, No. 66.2
 - IEC/EN 61558-1, IEC/EN 61558-2-2
 RoHS Compliant
FIELD INSTALLED OPTIONS 
CATALOG NUMBER
DESCRIPTIONS
Related Products
DIN Circuit Breaker Mounting 
  DIN Rail Power Supplies
 
SBEDIN
Field installed IEC fuse holder adaptor 
  63 Series Power Conditioners
kit
  Surge Protective Devices
Terminal Covers (Two Covers Per Kit)
IP20
Field installed primary and secondary 
IEC Touch Proof Cover Kit.
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.   
194
 January 2017Industrial Control Transformers
Selection Tables: International Series
Group 1   -/220/380 V Primary, 110/23 V Secondary, 50/60 Hz
 208/240/415 V Primary, 120/24 V Secondary, 50/60 Hz
 200/230/400 V Primary, 115/24 V Secondary, 50/60 Hz
Approx. 
Continuous Instantaneous Catalog Height Width Depth Mtg Width Mtg Depth Slot Size
Ship Weight  
VA VA Number in (mm) in (mm) in (mm) W1 / W2 - in (mm) D1 / D2 - in (mm) S1/S2 - in (mm)
lbs (kg)
2.96 3.39 4.36 2.81 / 2.50 2.10 / N/A .20 x .50 / .20 x .50
50 105 4.0 (1.82)
E050TC
(75.2) (86.1) (110.7) (71.4 / 63.5) (53.3 / N/A) (5.1 x 12.7 / 5.1 x 12.7)
3.89 4.50 4.48 3.74 / 3.12 2.56 / 2.87 .20 x .65 / .20 x .33
100 230 8.0 (3.67)
E100TC
(98.8) (114.3) (113.8) (95.0 / 79.3) (65.0 / 72.9) (5.1 x 16.5 / 5.1 x 8.4)
3.89 4.50 5.21 3.74 / 3.12 3.29 / 3.61 .20 x .65 / .20 x .33
150 420 E150TC 11.0 (5.00)
(98.8) (114.3) (132.3) (95.0 / 79.3) (83.6 / 91.7) (5.1 x 16.5 / 5.1 x 8.4)
4.53 5.25 5.07 4.38 / 3.75 3.54 / N/A .31 x .85 / .31 x .85
250 675 15.0 (6.82)
E250TC
(115.1) (133.4) (128.8) (111.3 / 95.3) (89.9 / N/A) (7.9 x 21.6 / 7.87 x 21.6
5.56 6.38 6.93 5.32 / 4.37 4.25 / 5.75 .31 x .03 / .31 x .85
500 1550 30.0 (13.64)
E500TC
(141.2) (162.1) (176.0) (135.1 / 111.0) (108.0 / 146.1) (7.9 x .85 / 7.9 x 21.6)
Group 2   208/240/415 V Primary, 24 V Secondary, 50/60 Hz
 277/480 V Primary, 24 V Secondary, 60 Hz
 200/230/400 V Primary, 24 V Secondary, 50/60 Hz
 220/380 V Primary, 23 V Secondary, 50/60 Hz
Mtg Width Mtg Depth Approx. 
Continuous Instantaneous Catalog Height Width Depth Slot Size
W1 / W2 D1 / D2 Ship Weight 
VA VA Number in (mm) in (mm) in (mm) S1/S2 - in (mm)
in (mm) in (mm) lbs (kg)
2.96 3.39 4.36 2.81 / 2.50 2.10 / N/A .20 x .50 / .20 x .50
50 105 4.0 (1.82)
E050TE
(75.2) (86.1) (110.7) (71.4 / 63.5) (53.3 / N/A) (5.1 x 12.7 / 5.1 x 12.7)
3.89 4.50 4.48 3.74 / 3.12 2.56 / 2.87 .20 x .03 / .20 x .01
100 230 8.0 (3.67)
E100TE
(98.8) (114.3) (113.8) (95.0 / 79.3) (65.0 / 72.9) (5.1 x .65 / 5.1 x .33)
3.89 4.50 5.21 3.74 / 3.12 3.29 / 3.61 .20 x .03 / .20 x .01
150 420 11.0 (5.00)
E150TE
(98.8) (114.3) (132.3) (95.0 / 79.3) (83.6 / 91.7) (5.1 x .65 / 5.1 x .33)
4.53 5.25 5.07 4.38 / 3.75 3.54 / N/A .30 x .71 / .30 x .71
250 700 15.0 (6.82)
E250TE
(115.1) (133.4) (128.8) (111.3 / 95.3) (89.9 / N/A) (7.9 x 18.0 / 7.9 x 18.0)
5.56 6.38 6.93 5.32 / 4.37 4.25 / 5.75 .30 x .85 / .30 x .85
500 1550 E500TE 30.0 (13.64)
(141.2) (162.1) (176.0) (135.1 / 111.0) (108.0 / 146.1) (7.9 x 21.6 / 7.9 x 21.6)
Note: Instantaneous VA calculated at At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
Design Style
Mounting Dimensions Profile Top View
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.   
195
 January 2017