Monitoring Relays
True RMS 3-Phase, 3-Phase+N, Multi-function
Types DPB01, PPB01
TRMS 3-phase over and under voltage,
phase sequence and phase loss monitoring relays
Detect when all 3 phases are present and have the
correct phase sequence (except for N versions)
Available versions (W4) supplied between phase and
neutral
Detect if all the 3-phase-phase or phase-neutral volt-
ages are within the set limits
Upper and lower limits separately adjustable
Measure their own power supply
Selection of measuring range by DIP-switches
Adjustable voltage on relative scale
Adjustable delay function (0.1 to 30 s)
DPB01 PPB01
Output: 8 A SPDT relay N.E.
For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DPB01) or plug-in module (PPB01)
22.5 mm Euronorm housing (DPB01)
or 36 mm plug-in module (PPB01)
LED indication for relay, alarm and power supply ON
Product Description
Ordering Key
DPB 01 C M23
3-phase or 3-phase+neutral points) with built-in time Housing
line voltage monitoring relay delay function. Function
for phase sequence, phase Supply ranges from 208 to Type
loss, over and under voltage 480 VAC covered by two Item number
(separately adjustable set multivoltage relays. Output
Power supply
Type Selection
Mounting Phase sequence Output Supply: Supply: Supply:
detection 208 to 240 VAC 380 to 415 VAC 380 to 480 VAC
DIN-rail yes SPDT DPB 01 C M23 DPB 01 C M48 W4 DPB 01 C M48
Plug-in yes SPDT PPB 01 C M23 PPB 01 C M48 W4
Plug-in yes SPDT PPB 01 C M48
DIN-rail no SPDT DPB 01 C M23 N DPB 01 C M48 N W4 DPB 01 C M48 N
Plug-in no SPDT PPB 01 C M23 N PPB 01 C M48 N W4
Plug-in no SPDT PPB 01 C M48 N
Input Specifications
Input Ranges
L1, L2, L3, N DPB01: Terminals L1, L2, L3, N Upper level +2 to +22%
PPB01: Terminals 5, 6, 7, 11 of the nominal voltage
Measure their own supply Lower level -22 to -2%
Note: Connect the neutral only of the nominal voltage
if it is intrinsically at the star Note: The input voltage
centre must not exceed the maximum
rated voltage or drop below
Measuring ranges
the minumum rated voltage
208 to 240 VAC 177 to 275 V AC
L-L
reported above.
M23 versions
380 to 415 VAC 323 to 475 V AC Hysteresis
L-L
PPB01CM48 Set points from 2 to 5% 1%
PPB01CM48N Set points from 5 to 22% 2%
D/P PB01CM48W4
D/P PB01CM48NW4
380 to 480 VAC 323 to 550 V AC
L-L
DPB01CM48
DPB01CM48N
Specifications are subject to change without notice (31.03.10) 1DPB01, PPB01
Output Specifications General Specifications
Power ON delay 1 s 0.5 s or 6 s 0.5 s
Output SPDT relay
Rated insulation voltage 250 VAC
Reaction time
Incorrect phase sequence or
Contact ratings (AgSnO)
2
total phase loss < 200 ms
Resistive loads AC 1 8 A @ 250 VAC
Voltage level (input signal variation from
DC 12 5 A @ 24 VDC
-20% to +20% or from
Small inductive loads AC 15 2.5 A @ 250 VAC
+20% to -20% of set value)
DC 13 2.5 A @ 24 VDC
Alarm ON delay < 200 ms (delay < 0.1 s)
6
Mechanical life 30 x 10 operations
Alarm OFF delay < 200 ms (delay < 0.1 s)
5
Electrical life 10 operations
Accuracy (15 min warm-up time)
(at 8 A, 250 V, cos = 1)
Temperature drift 1000 ppm/C
Operating frequency 7200 operations/h
Delay ON alarm 10% on set value 50 ms
Repeatability 0.5% on full-scale
Dielectric strength
Dielectric voltage 2 kVAC (rms)
Indication for
Rated impulse withstand volt. 4 kV (1.2/50 s)
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON LED, yellow
Supply Specifications
Environment
Power supply Overvoltage cat. III
Degree of protection IP 20
Rated operational voltage (IEC 60664, IEC 60038)
Pollution degree 3 (DPB01), 2 (PPB01)
through terminals:
Operating temperature
L1, L2, L3, N (DPB01)
@ Max. voltage, 50 Hz -20 to 60C, R.H. < 95%
5, 6, 7, 11 (PPB01)
@ Max. voltage, 60 Hz -20 to 50C, R.H. < 95%
Storage temperature -30 to 80C, R.H. < 95%
D/P PB01CM23, 208 to 240 V AC 15%
L-L
Housing
D/P PB01CM23N 45 to 65 Hz
Dimensions DPB01 22.5 x 80 x 99.5 mm
PPB01 36 x 80 x 94 mm
D/P PB01CM48W4, 380 to 415 V AC 15%
L-L
Material PA66 or Noryl
D/P PB01CM48NW4, (220 to 240 V AC 15%)
L-N
Weight Approx. 120 g
PPB01CM48, PPB01CM48N 45 to 65 Hz
Screw terminals
Tightening torque Max. 0.5 Nm
DPB01CM48, DPB01CM48N 380 to 480 V AC 15%
L-L
according to IEC 60947
(220 to 277 V AC 15%)
L-N
45 to 65 Hz
Product standard EN 60947-5-1
Rated operational power
Approvals UL, CSA
DPB01CM23x, PPB01CM23x 13 VA @ 230 VAC, 50 Hz
(except for W4 versions)
DPB01CM48x, PPB01CM48x 13 VA @ 400 VAC, 50 Hz
CCC (GB14048.5) only DPB
Supplied by L1 and L2
CE Marking L.V. Directive 2006/95/EC
DPB01CM48xW4
EMC Directive 2004/108/EC
DPB01CM48xW4 13 VA @ 400 VAC, 50 Hz
EMC
Supplied by L1 and N
Immunity According to EN 61000-6-2
Emissions According to EN 61000-6-3
Mode of Operation
Connected to the 3 phases flashing 2 Hz and the output Example 1 Example 2
(and neutral) DPB01 and relay releases after the set (mains network monitoring) (load monitoring)
PPB01 operate when all 3 time period. In any case if
phases are present at the phase-neutral measurement The relay monitors over and The relay releases in case of
same time, the phase is selected both phase- under voltage, phase loss interruption of one or more
sequence is correct (not N phase and phase-neutraland correct phase phases, when one or more
versions) and the phase- voltages are monitored. If sequence. voltages drop below the
phase (or phase-neutral) the phase sequence is In case of N versions, the lower set level or exceed the
voltage levels are within set wrong or one phase is lost, relay monitors over and upper set level.
limits. the output relay releases under voltage.
immediately.
If one or more phase-phase Only 200 ms delay occurs.
or phase-neutral voltages The failure is indicated by
exceeds the upper set level the red LED flashing 5 Hz
or drops below the lower set during the alarm condition.
level, the red LED starts