Multi-stage EMI Filter
Rated currents from 6 to 30 A Approvals
Surge pulse protection up to 2 kA
Solder or screw connection
Features and benefits
FN 352Z series is developed to meet high filter
attenuation requirements by using multi-stage filter
design
Additional high surge pulse voltage protection up
to 2 kA is integrated to protect sensitive equipment
Choosing FN 352Z product line brings you the rapid
availability of a standard filter associated with the
necessary safety acceptances
Standard filters are a practical solution helping you
to pass EMI system approval in a short time
Exceptional conducted attenuation performance,
based on multi-stage design and chokes with high
saturation resistance and excellent thermal behavior
Various connection options
Custom-specific versions on request
Technical specifications
Typical applications
Maximum continuous operating voltage 250 VAC, 50/60 Hz
Operating frequency dc to 400 Hz
Facility management
Rated currents 6 to 30 A @ 40 C max.
Industrial
High potential test voltage P > PE 2000 VAC for 2 sec
Telecommunication
P > N 350 VDC for 2 sec
Data processing
Energy absorption 40J
Electrical and electronic equipment
Temperature range (operation and storage) -25 C to +85 C (25/85/21)
Flammability corresponding to UL 94 V-2 or better
Typical electrical schematic
Design corresponding to UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
MTBF @ 40C/230V (Mil-HB-217F) 230,000 hours
Surge pulse protection 2 kV IEC 61000-4-52
EMC/EMI Products Schaffner Group Datasheets 2014
Filter selection table
Rated
Filter current Leakage current* Inductance Capacitance Resistance Energy Input/Output Weight
@ 40 C (25 C) @ 230 VAC/50 Hz L L1 L2 Cx Cx1 Cy Cy1 R absorption connections
[A] [A] [mH] [mH] [mH] [nF] [nF] [nF] [nF] [M] [J] [g]
FN 352Z-6-06 6 (7.2) 420 3 3 470 220 3.3 1.5 0.47 40 -06 575
FN 352Z-10-29 10 (12) 1300 5 0.06 0.003 220 220 15 15 0.47 40 -29 1320
FN 352Z-20-29 20 1300 3.5 0.06 0.0035 220 220 15 15 0.47 40 -29 2950
FN 353Z-30-33 24 (30) 1300 2.3 0.025 0.035 470 220 15 15 0.23 40 -33 3100
* Maximum leakage under normal operating conditions.
Note: if the neutral line is interrupted, worst case leakage could reach twice this level.
Typical filter attenuation
Per CISPR 17; A = 50 /50 sym; B = 50 /50 asym; C = 0.1 /100 sym; D = 100 /0.1 sym
6 A types 10 A types 20 A types 30 A types
Mechanical data
6 A types 10 and 20 A types
30 A types