Bussmann
Specialty Fuses GMW
Fast-Acting
and HWA
Dimensional Data
FUSE
0.69"
0.147" 0.28"
(17.5mm)
(3.7mm) (7.1mm)
0.25"
FRONT
0.55"
(6.4mm)
PANEL 0.98" (13.9mm)
(25.0mm)
CATALOG SYMBOL: GMW (FUSE), HWA (HOLDER)
PIN TYPE
0.280 x 0.25 (7.1mm x 6.4mm)
+ 0.002"
MOUNTING HOLE
Test Specifications
(0.5mm)
FAST-ACTING
0.379"
Load Opening Time
INTERRUPTING RATING - 35 AMPS (9.6mm)
100% 4 hrs. (min.)
GMW: U.L. RECOGNIZED
200% 10 sec. (max.)
(GUIDE #JDYX2, FILE # E19180)
HWA: U.L. RECOGNIZED
0.344"
(GUIDE #IZLT2, FILE # E14853)
(8.7mm)
Time-Current CharacteristicsTotal Clear
Electrical Ratings (Catalog Symbol and Amperes)
125 Volts
AMPERE
RATING
GMW-1/100 GMW-1/4 GMW-1-1/2
100
GMW-1/64 GMW-3/10 GMW-2
GMW-1/32 GMW-4/10 GMW-3
GMW-1/16 GMW-1/2 GMW-4
GMW-1/10 GMW-6/10 GMW-5
GMW-1/8 GMW-3/4
GMW-2/10 GMW-1
10
Carton Quantity and Weight
Ampere Carton Weight*
Ratings Qty Lbs. Kg.
GMW 1/1005 100 0.20 97.7
1
HWA Fuseholder 100 0.44 200.0
AF Knob 100 0.25 113.4
* Weight per carton.
Sub-miniature pin-base fuses for limited space applications.
.1
Can be soldered direct into circuit or can be mounted in
HWA holder which can be soldered into circuit.
Transparent window in fuse for visual determination of open
fuse element.
Fuseholder body and knob material is diallyl phthalate.
.01
Holder includes O-ring, gasket, and nut.
Military versions: fuseFMO1; holderFHN42W.
CURRENT IN AMPERES
Type HWA-AF holder includes waterproof cap (knob) AF.
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled. This bulletin is intended to
clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any
products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been select-
ed, it should be tested by the user in all possible applications.
Form No. GMW
12-18-98
Page 1 of 1
SB98107 Rev. A
BIF Doc #2058
TIME IN SECONDS
.005
1/200
.01
1/100
1/64
1/32
1/16
.1
1/10
2/10
1/4
3/10
4/10
1/2
6/10
1 3/4
1
1-1/2
2
3
4
5
10
30